Abstract

This study presents a novel adaptive droop control (ADC) strategy for power-sharing in a multi-terminal high-voltage DC grid while maintaining a desirable DC voltage level. The ADC scheme can share the power without burdening any power converters during one or more converter outages and huge power imbalance situations. To improve the effectiveness of the power sharing and DC voltage deviation control, the ADC is also implemented for wind farm converters. This is achieved through a derated mode operation of wind farms. The performance and effectiveness of the proposed control approach are evaluated in several case studies based on the specific type of converter outage under the various outage scenarios. The proposed method is validated on a five-terminal CIGRE B4 DC grid test system.