Abstract

Shunt active power filter (SAPF) has been widely used in active distribution network system. Improving the compensation performance of SAPF has become the focus of many scholars. The traditional filter interface usually adopts series resistance. In order to reduce the loss of damping resistance and ensure the compensation performance of SAPF, a new type of passive interface is adopted, and the double-loop control scheme of PI control combined with repeated control is adopted. By comparing the difference of the selected points of different feedback currents, when the feedback current is taken from the inverter, only a small damping resistance is needed to achieve good steady-state accuracy. Simulation results verify the correctness and effectiveness of the proposed scheme and the system feedback current selection method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.