Abstract
The gains of phase-locked-loop (PLL) and outer-loop control have significant impacts on the power transfer limits for the voltage source converter (VSC) connected to weak ac system. Therefore, in this paper, an enhanced control diagram with advanced outer-loop control is proposed. First, the P-V slope controller is proposed based on the participation factor analysis. Second, considering the overvoltage limitation, the maximum slope parameter is calculated. Third, Simulations and calculations validated the following two conclusions: 1) P-V slope control can improve the power transfer limitations of the VSC system. 2) considering the overvoltage limitation, the slope parameter of P-V control has the maximum value. With the proposed P-V slope control, the power transfer limits under both rectifier and inverter modes can be effectively extended.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.