Abstract

The Active Front-End (AFE) converter topology is generated by modifying a conventional back-to-back converter, from using a single VSC to use pVCS connected in parallel. The AFE configuration improves the capability, efficiency and reliability of energy conversion devices connected to the power system. In this paper, a novel technique to reduce the total harmonic distortion (THD) in an AFE converter topology is proposed and analyzed. The THD reduction is achieved by applying a phase shift angle in the SPWM switching signals of each AFE converter VSC. To verify the functionality and robustness of the proposed methodology, the power system simulation in Matlab-Simulink is analyzed for a type-4 wind turbine converter with total power output of 9MW. The obtained simulation results show a THD reduction up to 2.5 for AFE connected to the power network.