Abstract

The Active Front-End (AFE) converter topology is generated by modifying a conventional back-to-back converter, from using a single VSC to use pVCS connected in parallel. The AFE configuration improves the capability, efficiency and reliability of energy conversion devices connected to the power system. In this paper, a novel technique to reduce the total harmonic distortion (THD) in an AFE converter topology is proposed and analyzed. The THD reduction is achieved by applying a phase shift angle in the SPWM switching signals of each AFE converter VSC. To verify the functionality and robustness of the proposed methodology, the power system simulation in Matlab-Simulink is analyzed for a type-4 wind turbine converter with total power output of 9MW. The obtained simulation results show a THD reduction up to 2.5 for AFE connected to the power network.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.