Abstract
<para xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> IEEE Standard 1459–2000 establishes that in an efficient electrical system, only the fundamental positive-sequence active power must be present. This paper proposes a new set of reference currents based on the IEEE Standard 1459–2000 for the control of a three-branch four-wire shunt active power compensator. Reactive, unbalance, and harmonic distortion phenomena can be cancelled out upstream from the point of connection, achieving maximum efficiency of the three-phase four-wire electrical system. In addition, a new current control and a three-dimensional space vector pulsewidth-modulation technique are proposed to develop a shunt active power compensator. Simulation and experimental results demonstrate that the proposed shunt active power compensator improves the upstream electrical quality of the power network, achieving maximum efficiency according to IEEE Standard 1459–2000 specifications. </para>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.