Abstract
Inaccurate reactive power sharing and voltage distortion at the point of common coupling (PCC) always exist in a parallel inverter system due to feeder impedance mismatches and nonlinear load disturbances. An enhanced inverter control scheme through an output impedance adjustment is proposed to address these issues. Inverter output impedance is regulated considering fundamental and harmonic frequencies, and accurate power sharing and improved PCC voltage quality are realized at the steady state. In addition, the compensation scheme is easily applied in multiple parallel inverters without any prior knowledge of the feeder impedance. Experimental results with three parallel inverters validate the feasibility of the proposed control scheme.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.