Abstract

The sampling rate of the wide-area synchronous phasor measuring device (D-PMU) in the distribution network is insufficient, and the localization sensitivity of the traditional localization method based on the time-domain Bergeron equation in the distribution network is insufficient. In this paper, an accurate location method of the distribution line grounding fault based on the time-domain’ synchronous information calculation is proposed to solve the problem of limited location accuracy caused by a low sampling rate and the insufficient sensitivity of traditional methods. The method preprocesses the measurement data through low-frequency time-domain signal reconstruction and cubic spline interpolation. The fault current’s different location criterion is constructed by using the voltage and current constraints at the fault point. By calculating the fault current difference at a limited number of calculated points, the accurate fault location under a low sampling rate is realized, which is beneficial to the rapid maintenance of faults and the shortening of the power outage time.