Abstract

This paper presents verification of high voltage measuring systems by time convolutions between standard testing waveforms and unit step responses of the measuring systems. The waveforms under investigations are full lightning impulse voltage waveforms, tail-chopped lightning impulse voltage waveforms, front-chopped lightning impulse voltage waveforms and steep-front voltage waveforms according to IEC standards 60060-2 and 61211. This paper considers four different types of the measuring systems. The results show that this technique is applicable, and should be a useful method for impulse voltage measurements in a standard high voltage

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.