Abstract
This paper shows that the average and variance of the accumulated damage caused by earth-quakes on the piping system attached to a building are related to the seismic response factor λ. The earthquakes refered to in this paper are of a non-stationary random process kind. The average is proportional to λ2 and the variance to λ4. The analytical values of the average and variance for a single-degree-of-freedom system are compared with those obtained from computer simulations. Here the model of the building is a single-degree-of-freedom system. Both average of accumulated damage are approximately equal. The variance obtained from the analysis does not coincide with that from simulations. The reason is considered to be the forced vibration by sinusoidal waves, and the sinusoidal waves included random waves. Taking account of amplitude magnification factor, the values of the variance approach those obtained from simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series C
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.