Abstract

Based on the test results carried out in the multi-function artificial climate chamber of Chongqing University (China) on two types of composite insulator, this paper discusses the effects of atmospheric pressures or altitudes, contamination level and ice amount secreted on the minimum AC flashover voltages of composite insulators, and analyzes the flashover performance of the composite insulator in icing, contaminating and low pressure conditions. The authors therefore put forward a correction method of flashover voltages.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.