Abstract

According to the operation experience and investigation in China, the insulation performance of transmission line can be reduced due to the effect of strong rain, which is not considered in the external insulation design. Meanwhile, there is no correction reference regarding the breakdown voltage of air gap under rain conditions in IEC standards. Therefore, a series of experimental tests were conducted in the artificial climate chamber and at Xuefeng Mountain Natural Site with the usage of rod-plane air gap to analyze the relationship between ac breakdown voltage and rain precipitation rate, rain conductivity and ambient temperature. It is shown that the breakdown voltage of air gap decreases with an increase of rain precipitation rate and rain conductivity, and increases with an increase of ambient temperature. In addition, according to the test results, the correction formula of ac breakdown voltage of rod-plane air gap under rain condition is proposed and verified in this paper.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.