This paper gives the operating experience of some thousand miles of 132-kv. transmission lines analyzed from the lightning point of view. The lightning experience during three years operation of the system is compared. In addition, the effect of ground wires, grading shields, and tower footing ground resistances is discussed from data secured under operating conditions. The comparative reliability of single- and two-circuit lines is analyzed from the data recorded. Cases of damage to insulator strings, hardware, etc., are tabulated and discussed from the point of the severity of the damage and the location on the phase wires. Yearly averages of lightning outages per 100 mi. of line per year are given for the different lines and from these figures comparisons made for the different types of line construction. A three year record is given of the percentage of lightning outages on the 1000-mi. network.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.