Abstract
In order to reduce the weight of air-conditioner, a new type micro-channel heat exchanger is applied for heat pump system. The micro-channel heat exchanger has high performance compared with a conventional fin and tube type heat exchanger due to its characteristic configuration. However, there are some challenges, when the micro-channel heat exchanger is applied for heat pump system. One of the most difficult problems is to improve the drainage of condensed water when it is used as an evaporator. To solve this problem, a new shape fin named "Insertion waffle louver fin" is proposed. In addition, the specifications of the heat exchanger, such as louver configurations and tube arrangement, are optimized for heat pump system. As a result, the micro-channel heat exchanger can reduce the weight about one third and the amount of containing remgerant about one fourth compared with a conventional fin and tube type heat exchanger
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Proceedings of the Thermal Engineering Conference
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.