Abstract
In recent years, the heat flux of electronic devices has significantly increased due to higher output and downsizing. A JEST type Loop Heat Pipe with a water-cooled heat exchanger has been developed. In the present study, the total thermal resistance was divided to each part of the equipment, and the effect of each thermal resistance on the cooling performance was investigated. As a result, the effect of vapor line inner diameter on the total thermal resistance was clarified. And it was also revealed that the evaporator thermal resistance was 65% of the total thermal resistance. Therefore, an approach to decrease the evaporator thermal resistance is effective for improving the cooling performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: The Proceedings of the Thermal Engineering Conference
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.