Abstract

Regarding the initial value sensitivity issues commonly found in Newton-like power flow calculation algorithms, a zero-injection initialization numerical method for ill-conditioned power flow is proposed in this paper, which improves the convergence of power flow calculation in ill-conditioned power systems. Based on the initial power flow provided by this method, the unbalanced active power of each bus (the slack bus excluded) relates to the net injection of active power of that bus and the unbalanced reactive power of each PQ bus relates to the net injection of reactive power of that bus, thus avoiding significant power unbalance. The method put forward herein can provide a reasonable initial value for the power flow calculation so that difficulty in power flow convergence caused by the unreasonable initial power flow is effectively avoided. The Newton’s method and the optimal multiplier method are implemented respectively on a small-scale ill-conditioned test system to verify the feasibility of the proposed zero-injection initialization numerical method.