Abstract

Summary form only given, as follows. This paper presents the development of a wavelet-based scheme, for distinguishing between transformer inrush currents and power system fault currents, which proved to provide a reliable, fast and computationally efficient tool. The operating time of the scheme is less than half power frequency cycle (based on 5 kHz sampling rate). In this work, a wavelet transform concept is presented. Feature extraction and method of discrimination between transformer inrush and fault currents is derived. A 132/11 kV, transformer connected to a 132 kV power system were simulated using EMTP. The generated data were used by the MATLAB to test the performance of the technique as to its speed of response, computational burden and reliability. The proposed scheme proved to be reliable, accurate and fast.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.