Abstract
This paper presents a new wavelet-based busbar differential protection algorithm, named as 87BW function. The instantaneous current-based differential protection fundamentals are taken into account and the well-known 1-out-of-1 and 2-out-of-2 tripping logics are mapped into the wavelet domain. Operating and restraint wavelet coefficients energy of currents are computed, regarding station configuration and bus zones boundaries. Thereby, the proposed 87BW function can be properly used in both static and dynamic busbar configuration. Its performance was evaluated through EMTP-based simulations of faults in a 230 kV power substation with double bus single breaker configuration. The obtained results reveal it provides ultra-high-fast trip for internal and evolving external-to-internal faults, guaranteeing security for normal through-load and external faults as well, even in the case of early and severe current transformer saturation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.