Abstract

Summary In this paper, a Two-Step Hybrid State Estimator based on classical SCADA and new phasor measurement unit inputs is presented. The first step is a linear state estimator that utilizes only synchrophasors. The second step is an iterative state estimator that combines conventional measurements with pseudo-measurements obtained from the first step. The developed hybrid model takes advantage of the high sampling frequency of the synchrophasors by running the first step state estimator several times between two consecutive runs of the second step state estimator. The methodology was tested on the IEEE 14 and 57 buses test systems and the real full Croatian transmission power system model. It was also compared with other hybrid models. The proposed formulation of the hybrid state estimator is comparable with other hybrid models in view of accuracy and convergence, and it offers enhanced filtering of measurement errors. Copyright © 2014 John Wiley & Sons, Ltd.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.