Abstract

A novel active damping strategy for the LCL filter resonance is proposed using the grid current and the capacitor voltage. The proposed technique is deduced in the continuous time domain and a discussion for its discrete implementation is presented. According to the proposed technique, instability of the open loop system, which results in non-minimum phase behavior, can be avoided over wide range of resonant frequencies. Moreover, straightforward co-design steps for both the fundamental current regulator and the active damping loops can be used. A numerical example along with experimental results are introduced to validate the proposed strategy performance over wide range of resonant frequencies.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.