Abstract
This paper presents a single-ended traveling wave based fault location method for power transmission systems where overhead lines are combined with underground cables. Bewley diagrams are used to determine the traveling wave patterns. The proposed method utilizes Discrete Wavelet Transform (DWT) to extract the transient information from the recorded voltage signals. The squares of the wavelet transform coefficients (WTC <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> ) are calculated in order to determine the energy of the signal which is used to identify the faulted section (underground cable or overhead line) and subsequently to locate the fault. The transient voltages for different types of faults and locations along the overhead section as well as the underground cable section are obtained through EMTP simulations. MATLAB Wavelet Toolbox is used to process the simulated transients and apply the proposed method. The performance of the method is tested on various scenarios.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.