Abstract
The parallel transmission lines on the same tower and six-phase transmission system both have the characteristic of narrow corridor, less occupied fertile soil and large transmission capacity, so they have been widely applied and laid great attention. The WAMS provides a new technical means for the safe and stable operation of six-line transmission system. Based on electrical signals of transmission lines gained from WAMS, this paper uses long line equation to calculate fault current, and analyzes the fault current with six sequence components method. On basis of magnitude and angle characteristic of six sequence components, a theory of fault phase selection for six-line transmission system is proposed. Theoretical analysis and EMTDC simulation tests show that this method is not affected by distributed capacitance and transition resistance, and can correctly select the fault phase at any case of operation mode and fault condition. It can provide effective fault phase selection logic for distance relay protection of six-line transmission system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.