Abstract

This paper reports a techno-economic comparison between a ground-coupled heat pump (GCHP) system and an air-coupled heat pump (ACHP) system. The systems connected to a test room in Firat University, Elazig (38.41°N, 39.14°E), Turkey, were designed and constructed for space cooling. The performances of the GCHP and the ACHP system were experimentally determined. The experimental results were obtained from June to September in cooling season of 2004. The average cooling performance coefficients ( COP sys ) of the GCHP system for horizontal ground heat exchanger (HGHE) in the different trenches, at 1 and 2 m depths, were obtained to be 3.85 and 4.26, respectively and the COP sys of the ACHP system was determined to be 3.17. The test results indicate that system parameters can have an important effect on performance, and that GCHP systems are economically preferable to ACHP systems for the purpose of space cooling.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.