Abstract

Transformers in power system usually take current differential protection as the main protection, but the protection is easy to be affected by inrush currents and then maloperates. Sympathetic inrush is one kind of inrush currents, which is caused by energization of an adjacent transformer. There were many transformer differential protection maloperation cases caused by sympathetic inrush in the field, while the conventional second harmonic restraint method did not work effectively. In this paper, a method based on substation-area currents and curve fitting is proposed to identify sympathetic inrush. The method is presented using the characteristic that sympathetic inrush and initial inrush alternatively appear in reverse polarities. The characteristic exists continuously during sympathetic inrush. In order to verify effectiveness of the proposed method, PSCAD/EMTDC software is used in this paper to build sympathetic inrush model and obtain simulation data. Simulation results prove that the proposed method can effectively identify sympathetic inrush.