Abstract

The increasing use of renewable generation, power electronic devices, and nonlinear loads in power systems brings more severe interharmonic tones to the measurand, which can increase estimation errors of P-class PMUs, cause misoperation of protection relays, and even threaten the stability of the power systems. Therefore, the performance of the P-class synchrophasor estimator under interharmonic interference should be evaluated and new estimation schemes that can improve the operational robustness are needed for various protection and control applications. In this paper, a synchrophasor estimator design for P-class PMUs that introduces singular value decomposition to the least square algorithm based on the Taylor series is proposed. By constructing an optimization with proposed adjustable parameters, finite impulse response filters with high transition band attenuation are designed. Numerical and experimental tests verify the proposed dynamic synchrophasor estimator performance and show an effective improvement in rejecting interharmonic tones, especially when a short time window and light computational burden are required.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.