Abstract

The results of tests of a short-circuit resistive switching superconducting fault current limiter (SFCL) for dc mains with maximum voltage of 4.1 kV and rated current of 4 kA have been considered. The superconducting unit and automatic high-speed vacuum breaker are key components of the SFCL. The superconducting unit consists of eight series-parallel connected modules, each of which contains four parallel high-temperature superconducting (HTSC) tapes. The tests of the SFCL have been carried out under simulations of short-circuit current with maximum current of 20 kA (maximum rate of current rise is 2500 A/ms) at a voltage of 4 kV. The tests have shown the ability of SFCL to limit the current up to 4 kA and turn it off 5 ms after the starting the mode of current limitation. The mean temperature of a HTSC tape reached up to 190 K at a duration of current limitation of 5 ms, which is in the range of allowed temperatures (lower than 290 K). The time to restore superconductivity of SFCL after turning off the current was no higher than 0.3 s.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.