The air solar heating system installed in Module 6 at the Alberta Home Heating Facility has an 11-m 2 double-glazed, south-facing solar collector tilted at 68°, a 2-m 3 rock storage unit, one air handling unit, motorized dampers, a two-stage electric furnace, and a system controller. The performance of the system was calculated by comparing the difference in electric power required for Module 6 and Module 5, a module of similar construction, and using the measured solar energy collected and the electric power required by Module 6. The monthly solar fraction ranged from 0 to 70%. The dynamic behavior of the solar collector was also studied.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.