Abstract

For some power grid topologies, there will be limitations in coordination for voltage correction based inverse time overcurrent protection. To solve this problem, the above limitations are analyzed at first in this paper. Then based on substation area information sharing, this paper proposes to use the voltage information of the high side of transformer to dynamically compensate for the inverse time characteristic curve equation, which can effectively compensate for the limitations of voltage correction based inverse time overcurrent protection scheme, and improve the properties of inverse time overcurrent protection significantly. The theoretical analysis and simulation results show that the proposed scheme has the feasibility and good practical value.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.