Abstract
The water level control system of the steam generator in a pressurized water reactor and its control problems are analysed. In this work, a stable control strategy during low power operation and transient states is studied. The control strategy employs substitutional information using the bypass valve opening instead of incorrectly measured signal at the low flow rate as the fuzzy variable of the flow rate during low power operation, and includes the flexible scale adjusting method for fast response at a large transient. A practical self-tuning algorithm based on the control performance and the descent method is also suggested and applied to tuning the membership function scale of the flow error.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.