Abstract

It is shown that the hourly ambient temperature and load of a substation transformer in Manitoba, observed over the three-month winter or summer time window, are governed by the normal distribution, respectively, and they jointly follow the bivariate normal distribution. Based on this, a rigorous model for the peak-load ambient temperature (i.e., the ambient temperature at the time when the winter or summer peak-load of the transformer occurs) is developed. This makes it possible to accurately determine the peak load capability of the transformer if its historical hourly ambient temperature and load data are available.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.