Abstract

In Korea, considering that the accuracy of fire scenario evaluation is reduced by performance-based design, it is assumed that the sprinkler does not operate. In other countries, the design continues to be researched considering the operation probability of the sprinkler. In particular, the operation probability that divides the effect after operation is analyzed. Therefore, the operation probability was analyzed by considering the effect of sprinkler operation using domestic fire statistics. As a result, it was found that the probability of successful operation for fire extinguishment was 44%, the success of suppression was 32%, and failure to operate was 24%. As a result of a comparison with data from other countries, the probability of operating, 76%, was lower than that of studies from other countries. When comparing the probability results for successful fire extinguishment, success of suppression, and failure to operate, it was confirmed that the probability of successful suppression was slightly different.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.