Abstract

Abstract Due to the lack of suitable evaluation systems for heating, ventilation, air-conditioning (HVAC) systems with ground source heat pump (GSHP) and energy storage (ES) technologies, it is difficult to design a building HVAC system to achieve optimized design with regard to investment cost, energy saving and environmental protection. This is a study on developing a fuzzy evaluation system by including GSHP and ES with comprehensively determined weights into an HVAC system. A questionnaire method was used and the answers from 21 HVAC experts were analyzed to facilitate the modeling. Taking a commercial integrated project in Nanjing as an engineering case, the evaluation system was tested. If the system with a comprehensive merit value of 0.303 is adopted, the annual operating cost is reduced by 32.5%, the annual total life cycle cost is reduced by 26.5% and the primary energy consumption and carbon emissions are reduced by 10.5%, with the initial investment increased by 6.5%. This study revealed that the newly developed evaluation system is very useful for realizing the optimal design of HVAC systems.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call