Abstract

AbstractGround resistance of high voltage substations must be as low as possible for safe grounding of their equipment both during normal and fault conditions. However, in gas insulated substations (GIS), even though resistance is low, it does not ensure the step and touch potentials of the grounding system within permissible levels. In the present study, an analytical model has been developed to calculate ground resistance, step and touch potentials of a grounding system used for GIS. Different models have been proposed for the evaluation of number of grounding rods to be inserted in to the ground. The effect of concrete foundations on above performance parameters has been analyzed by considering various fault currents, soil/earth resistivities and number of grounding rods. Finally, design optimization of GIS grounding system has been reported for fault currents in the order of 63 kA located in earth resistivity of 100Ω-m and above.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.