Abstract

This paper reports a study on determining the steady-state voltage stability limit of interface flow on a set of interface lines between the metropolitan region and the neighboring regions in the Korea Electric Power Corporation (KEPCO). The interface flow limit considering severe contingencies is determined with a concept of interface flow margin, which is the active power flow margin of the key transmission lines between one region and others under a fixed load demand condition. The paper proposes a procedure to determine secure limit of active power flow on a set of specified interface lines. The procedure uses the modified continuation power flow (MCPF) tracing a path of power flow solutions with respect to generation shift to vary interface flow. In simulation, voltage stability limits of the metropolitan interface flow of the 1998 KEPCO system are determined.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.