Abstract

This study investigated the pressure drop and heat transfer characteristics of heat exchanger according to the arrangement of fins as well as fin configuration by the similitude experiments with the finned-tube geometry scaled as large as four times. Colburn j factor, Fanning friction factor, f, and goodness factors are compared to each other to estimate performance of each case for four different kinds of fins, which are louver, double side slit, single side slit and plain fin. Results show that heat transfer would be altered by fin arrangement and that friction loss is more affected by fin configurations than by the fin arrangements. In particular, heat transfer depends more on the shape of front row than that of rear row. The heat transfer rate of combined fin arrangement increases a lot more under the same pressure drop than that of conventional fin arrangement. This indicates that the heat exchanger of higher efficiency would be designed by the proper combination of fins of different shapes.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.