Abstract

The electric power required to operate the urban railway supplies DC 1,500 V to the electric train through trolly wire. The rectifier which converts AC to DC has a rectification method using a diode and a rectification method using a thyristor. The thyristor rectification method is easier to adjust the trolly wire voltage than the diode rectification method. In addition, it is possible to reuse the regenerative electric power generated when the electric train stops, thereby helping to reduce the operating cost of the Urban railway operator and to reduce the greenhouse gas. However, the thyristor rectification method has a disadvantage in that the power factor of an urban railway substation is lowered because a harmonic current is generated during rectification and the reactive power becomes large. In this paper, we analyze the harmonic currents generated of Busan Urban railway substation system using thyristor rectifier, we propose an optimal harmonic filter to achieve a power factor of over 90% by simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.