Abstract
Among the hazards posed to storage tanks by thermal radiation are the effects of changes in the mechanical strength of the metal at high temperatures that may lead ultimately to failure. Alarge-scale experimental study has been made of the water cooling requirements for metal surfaces exposed to thermal radiation. A two meter square radiation furnace and commercial water spray equipment were used in the study, which included trials on both vertical and inclined target surfaces. Water application rates between 1.4 and 10.4 L/min per square meter and incident heat fluxes up to 70 kW per square meter were employed. The experimental work was supported by a theoretical model of the cooling process.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.