Abstract

This study performed at Columbia College Chicago (CCC) had two purposes: The first was to test the functionality of the recently developed real-world transmission loss (RWTL) chamber, while the second was to evaluate the performance of the Kinetics UniBrace-L product on a double wall construction assembly. CCC’s RWTL chamber is designed to illustrate issues that have influence when testing partitions in the field. It is smaller in volume than a certified STC chamber, which results in modal effects on both sides of the chamber. Numerous microphone positions are available and are used to display the modal effects of the rooms and to determine an average sound pressure level in both spaces during testing. Absorption values are also substantially different between the sending and the receiving spaces (each side can be switched as either sending or receiving room) and diffuse-field conditions are not achieved in either side of the chamber. As such, the RWTL chamber will typically yield a lower STC value than a certified STC Chamber and will also yield lower values than what may be experienced when performing a test that would follow the standard ASTM E-336 or associated procedures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call