Abstract

A robust H ∞ controller for the feedwater system of KSNP (Korean Standard Nuclear Power Plant) vertical U-tube type steam generators (UTSG) is presented herein. As the first step of the controller development, a precise thermal–hydraulic model for the steam generator is built. A series of model experiments are performed using the developed thermal–hydraulic model in order to acquire the input–output data sets which represent steam generator characteristics. These data sets are utilized to build simplified steam generator models for control through a system identification algorithm, Simple Process Models. Among the developed steam generator models, the representative models for the designated power ranges are selected by a criterion of ν-gap metric. The representative robust controllers for the selected models are designed utilizing the loop-shaping H ∞ design technique. Finally, the robustness and performance of the proposed controllers are validated and compared against those of PI (proportional–integral) controller. The validation results demonstrated that the proposed H ∞ robust controller has a superior robustness and an enhanced control performance.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call