Abstract

Buildings constructed of cold-formed steel members are increasingly used in many countries. In recent years, cold-formed steel shear walls with steel sheathing were introduced as lateral force resisting systems. Design provisions of these structures require that the shear strength of shear walls with a height to width aspect ratio (h/w) greater than 2:1 be reduced by the factor 2w/h for satisfying allowable story drift limit. In this research, the accuracy of the factor is investigated using the results of previous tests and the tests performed by the researcher. Results show that the reduction factor (2w/h) is conservative. Thus, a relation is proposed for the reduction factor.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.