Abstract
Abstract The performance of algorithms for fault location is directly related to the accuracy of its input data. Thus, factors such as errors in the line parameters, failures in synchronization of oscillographic records and errors in measurements of voltage and current can significantly influence the accuracy of algorithms that use bad data to indicate the faults location. This paper presents a methodology for fault location based on the theory of state estimation in order to determine the location of faults more accurately by considering realistic systematic errors that may be present in measurements of voltage and current. The methodology developed is innovative because, besides calculating the most likely fault distance obtained from measurement errors, the variance associated with the distance found is also determined, using the errors theory. The obtained results are relevant to show that the proposed estimation approach works even adopting realistic variances. Moreover, the fault location brings performance gains compared to a traditional algorithm, available in the literature.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.