Abstract
This paper proposes an improved variable step size kwong least mean square algorithm based single phase double stage solar photovoltaic (SPV) grid interactive system. The interconnection of the distribution system with the SPV system and the load invariability introduces harmonics in the grid current and voltages at the point of interconnection (POI). The double stage topology includes two power stages, the maximum power point tracking (MPPT) power stage where the peak solar power is extricated with subsistence of a boost converter. However, the voltage source converter in the second power stage aids feeding of active power in to the grid and improves the harmonic profile of the system. This control scheme is applied for the adaptive noise cancellation with faster convergence rate and harmonic suppression features. A hardware prototype is developed for the proposed system configuration and is tested under various abnormal conditions to validate system performance. Moreover, the test results conform well to the IEEE standard 519.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.