Abstract

The growth of Lithium Bromide–Water (LiBr–H2O) absorption based heat pump is encouraged for the necessity of extracting high heat from the electronic chips. This paper presents a simulation study of single-stage LiBr–H2O vapor absorption heat pump for chip cooling. In this study, a detailed thermodynamic analysis of the single-stage LiBr–H2O vapor absorption heat pump for chip cooling in the nonexistence of solution heat exchanger was performed and a user-friendly graphical user interface (GUI) package including visual components was developed by using MATlab (2008b). The influence of chip temperature on COP (Coefficient of Performance), flow rates and conductance was examined by using the developed package. The model is validated by using the values available in the literature and indicates that there is a greater reduction in the absorber load. The influence of chip temperature on the performance and thermal loads of individual components was studied and it was concluded that, COP increases from 0.7145 to 0.8421 with an increase in chip temperature.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.