Abstract
We report a LDC (load duration curve) method to determine the optimum size of CHP (combined heat and power) units. The method gives the appropriate capacity graphically from the LDC of a building's heating demand. The method can be applied to the most common CHP units that are connected to the electrical grid, installed with thermal storage and auxiliary heat sources, and operated by a traditional heat-led strategy. The LDC method is simple and requires less information than existing sizing methods. Our method is in agreement with existing methods within 2.7–12.6% for internal combustion engine-driven CHP units, and 17.1–32.1% for Stirling engine-driven CHP units.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.