Abstract

Polychlorinated biphenyls (PCBs) were broadly applied worldwide as electrical insulators in transformers and power capacitors, due to their high dielectric constant and non-flammability. They were often added to mineral oils (MOs) and used as dielectric fluids, which are nowadays classified as hazardous waste. Indeed, the Stockholm Convention aims to eliminate the use of equipment with PCB content greater than 0.005 wt-% (=50 ppm) by 2025. Accurate identification and quantification of small traces of PCBs contained in MO thus represent a great analytical challenge. To achieve this goal, a simple, cost-effective and fast chromatographic process was developed to separate PCBs from MO, allowing to obtain reliable data to determine the concentration of PCBs, reduced to 2-3 ppm. Experimental and analytical methods, such as thin layer chromatography, column chromatography as well as gas chromatography coupled with mass spectroscopy, were applied to acquire a high level of qualitative and quantitative determination of PCBs in transformer MOs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.