Abstract

A simple, low-cost, constant frequency, analog controller is proposed for the front-end half-bridge rectifier of a single-phase transformerless UPS system to maintain near unity power factor at the input and zero dc-offset voltage at the output. The controller generates the required gating pulses by comparing the input current with a periodic, bipolar, linear carrier without sensing the input voltage. Two voltage controllers and a single integrator with reset are used to generate the required carrier. All the necessary control operations can be performed without using any PLL, multiplier and/or divider. The controller can be fabricated as a single integrated circuit. The control concept is validated through simulation and also experimentally on an 800 W half-bridge rectifier. Experimental results are presented for ac-dc application, and also for ac-dc-ac UPS application with both sinusoidal and nonlinear loads. The simulation and experimental results agree well