This article presents a new systematic technique for identifying voltage traveling waves (TWs) to determine the location of line faults in half-bridge modular multilevel converter-based high-voltage dc (HBMMC-HVdc) grids. In this technique, the buffered voltage signal frame around the fault-detection time is first scaled and then segmented via an optimization process. Finally, the incident/reflected TWs arrival times are obtained by executing a simple search algorithm on the reconstructed signal segments’ differences. This article describes how to use this technique in three forms of TW-based fault location schemes, including the single-ended scheme with known TW velocity, the double-ended scheme with known TW velocity, and the double-ended scheme with unknown TW velocity. The application results on a four-terminal HBMMC-HVdc grid simulated with exact component models show the proposed technique’s high capability and accuracy in all the three TW-based fault-location schemes. According to these results, the average fault-location errors are less than 0.5% for all the schemes. The numerical results also confirm that the proposed technique maintains its excellent performance, even in the face of close to terminal faults with distances down to 4 km, faults with high resistances up to <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">$450 \Omega $ </tex-math></inline-formula> , and noisy signals with signal-to-noise ratios down to 55 dB. Moreover, the comparison results confirm that the proposed approach is more tolerant of measurement noise than the wavelet transform.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call