Abstract

Grid-connected inverters are the key part in renewable energy power generation systems. Usually, phase-locked loop (PLL) is adopted in grid-connected inverters to achieve synchronization. However, prior-art works have revealed that the negative resistance behavior in the low-frequency band caused by PLLs may lead to system instability under weak grids. In this paper, first, a comprehensive small-signal output impedance modeling of the LCL-filtered single-phase grid-connected inverter is derived for stability analysis, where the digital control delays and PLL dynamics have been taken into account. Then, a simple but effective virtual series based impedance reshaping method is proposed. With that, the inverter system can operate stably even under a very weak grid (e.g., short-circuit ratio (SCR) is as low as 1.2). Compared with the traditional grid impedance compensation by virtually increasing grid resistance or reducing the grid inductance, the proposed method does not require grid impedance estimation and is robust against system parameter variations. Thus, its feasibility is improved. Finally, experimental tests are carried out on a single-phase 5-kW prototype, validating the effectiveness of the proposed scheme.