This paper presents a new, simple and low cost method to reduce inrush currents caused by transformer energization. The method uses a grounding resistor connected at a transformer neutral point. By energizing each phase of the transformer in sequence, the neutral resistor behaves as a series-inserted resistor and thereby significantly reduces the energization inrush currents. The proposed method has been tested by computer simulation and laboratory experiments. Both results show that the method has a performance similar to that of the resistor pre-insertion scheme. The proposed method is much less expensive, however, since there is only one resistor involved and the resistor carries only a small neutral current in steady-state.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.