Abstract

This paper describes the derivation of a salient-pole synchronous generator harmonic model in the form of a harmonically coupled impedance matrix. In sequence components, the relationship between the generator harmonic voltages and currents in the presence of saliency can be represented by analytical expressions, which are derived from the normally available machine parameters such as direct and quadrature-axis subtransient reactances. Magnetic saturation reduces the rotor angle which leads to changes in the harmonic cross couplings. The generator model is validated by means of time domain simulations and the results from three-phase harmonic measurements of a direct connected generator-HVDC converter unit.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.