This paper presents a RTDS model applied to simulate periodic commutation impulse voltage of HVDC convent valve. The model’s main configure and basic parameters are matching to a typical monopole system which include 12-pulse converters of rectifier and inverter, convert-transformers, DC transmission line, DC filters and AC equivalent power network. Among the system model, the valve components of rectifier are User-Define-Component (UDC) model with RC branch for describing detail valve internal. And also, discrete time step apply 2.5μS non real-time of RTDS for complying with high frequency transient. The validation test is carried out and the result show that the model can simulate accurately valve voltage waveform.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.